Application:
This instrument is widely used for industrial process measure and control, which all secondary instrument can compatible with. It is the first choice for many industries and very widely used multi-function instrument.
Features:
It can accept all standard 1~5V, 0~5V, mV voltage signal, standard 4~20mA, 0~10mA, 0~20mA current signal, standard sensor .
It is compatible with pt100, Cu100, Cu50, BA1, BA2,G53, K couple,,S couple,R couple,B couple,N couple,E couple,J couple,T couple,
It can measure, change, calculate, display, record, save, communication and control many physical parameters, composition parameter.
Tens of engineering unit meet requirements of many industries
128×64 dot matrix display screen, chinese/english menu display for selection
Multi parameter display instantaneous value, accumulative value, engineering unit, alarm information, realtime clock, realtime
curve,historical curve, USB status, power off information.
Additional function of rooting , small signal cut
Memory funtion when power off, it can save the latest 6 times power off time and time period
high-speed, high-efficiency network communication interface
4M internal storage space for measure record save, it can save two hundred and sixty thousand times data.
Model: DNG-8310
Function: Temperature measurement, pressure measurement,
level measurement, flow measurement, element
measurements and etc. The transmitters, sensors,
hot resistance/ thermocouple which can offer standard
mA, mV, V signal.
Voltage signal: 1~5V、0~5V、mV voltage signal
Current signal: 4~20mA、0~10mA、0~20mA
Temperature compensation component:
hot resistance:Pt100、Cu100、Cu50、BA1、BA2、G53
Thermocouple:K couple、S couple、R couple、B couple、N couple、E couple、J couple、T couple
Instantaneous data display range: 0~9999, position of decimal point could be set
Accumulative data display range: 0~99999999,position of decimal point could be set
Engineering unit: ℃、RH%、MPa、kPa、Pa、kN、N、kg、mm、m、
m3、V、A、mA、mV、m3/h、Nm3/h、t/h、l/m、
kg/m、ppm、ppt、ppb、μS/cm、mS/cm、S/cm、
kΩ·cm、MΩ·cm、pH、%、mg/l、μg/l、mol/l、
mmol/l
Digital communication: RS485 general line
Alarm output:
high / low limit alarm, OC of measurement output, voltage less than 30V, current less than 50mA
Basic error: ≤±0.2%FS
Record volume: 4MB
Environment condition: temperature: 0-50℃ humidity : ≤90%RH
Power supply: AC/DC 24V±15%
Protection level: IP65
Outline dimension: 96mm×96mm×105mm(H×W×D)
Hole size: 91mm×91mm(H×W)
Fix mode: panel mounted
|
??????? ???????? ?????? ?????
????? ?????? 03-6764586
?? ???? 03-6771280 |